Архив в PDF формате
Дата публикации статьи в журнале: 2020/03/16
Название журнала: Восточно Европейский Научный Журнал, Выпуск:
54, Том: 5,
Страницы в выпуске: 63-66
Анотация: Residual life and heat control method of a turbogenerator stator winding insulation based on the regular heat control data and the temperature excess regressive dependences for load conditions parameters is presented. It is shown, that the reliability for insulation residual life definition of a generator stator windings is higher when the calculated value of maximum temperature is taken for the insulation temperature, rather than the resistance thermometers readings installed in the slots
Ключевые слова:
powerful turbogenerator
end zone
control
diagnostics
stator core
stator winding insulation
temperature
temperature
Данные для цитирования:
Kuchynskyi K.A.,
Kramarskyi V.A. ,
Hvalin D.I. .
RESIDUAL LIFE AND HEAT CONTROL OF A TURBOGENERATOR STATOR WINDING INSULATION (63-66). Восточно Европейский Научный Журнал. Технические науки. 2020/03/16;
54(5):63-66.